Elgar GUPS 2400A

GUPS 2400A

Elgar GUPS 2400A - Image 1 of 0
Elgar GUPS 2400A - Image 2 of 0
Elgar GUPS 2400A - Image 1 of 0
Elgar GUPS 2400A - Image 2 of 0
Elgar GUPS 2400A - Image 1 of 0
Elgar GUPS 2400A - Image 2 of 0

Elgar GUPS 2400A, Fuente de Poder Robusta e Ininterrumpible, Entrada AC, 2400 VA con Módulo de Batería Interna

Ametek
$
Codigo del Producto: GUPS-2400A
8 a 10 semanas
Los GUPS de Elgar son fuentes en-línea ininterrumpibles robustas que aceptan un amplio rango energía de entrada AC suministrada y militar. Sin intervención del operador, seleccionan automáticamente los rangos apropiados de energía de entrada para adaptarse a una operación global.

La serie GUPS ha sido diseñada específicamente para soportar la severidad de las aplicaciones móviles. Cumplen con los requerimientos de vibración y golpes especificados en MIL-STD-810E, Métodos 514.4 y 516.4. Su chasis de aluminio montado en rack con hardware de acero inoxidable soporta ambientes difíciles y proporciona un encapsulado fuerte y liviano.

  • Robusto
  • Entrada amplia (global)
  • Batería de respaldo en-línea
  • Suprime transitorios (picos)
  • Suprime sobretensión
  • Eliminación de distorsión de entrada
Output
Output Voltage GUPS 2400A115 VAC ±2% over full range of line and load variations
Output Voltage GUPS 2400U115 VAC or 230 VAC ±2% over full range of line and load
Output Frequency GUPS 2400A60 Hz ±0.1%
Output Frequency GUPS 2400U50 Hz or 60 Hz ±0.1%
Efficiency70% from AC input
Output Current21 ARMS, 63A peak
Output Distortion2% maximum THD with linear loads
Output Power2400 VA into ±0.8 PF load
Output Overload150% for 30s; 150% to 200% for 3s
AC to DC CrossoverIf AC input falls below or rises above the currently selected input range limits, the unit switches to battery. The GUPS 2400A-104 variant providing a three phase input from 159-232 VAC line to line at frequencies from 370-430 Hz is also available. Contact Elgar for details on this model.
Power Loss During CrossoverNone
Input
Input Voltage, AC85 to 140 VAC or 170 to 280 VAC Single Phase
Input Current, AC33A at 120 VAC, 17A at 240 VAC
Input Frequency, AC45 to 450 Hz
Internal Battery Module192 VDC, 2.5 AH. Optional external battery packs available
Battery Hold-Up Time5 minutes for internal module with 2400 VA load, 0.8 PF @ 25°C. Adding one external battery pack increases time to a minimum of 18 minutes at full rated load. Reduced loads increase backup time.
Environmental
AltitudeOperating 0 to 10,000 ft; non-operating 0 to 40,000 ft
TemperatureOperating 0° to 40°C; non-operating -40° to 65°C
Humidity5 to 95% non-condensing
General
Weight GUPS 2400A78 lbs, maximum without battery module. Removable internal battery module is 48 lbs (126 lbs max combined weight). GUPS 2400A-104 variant (123 lbs max combined weight).
Weight GUPS 2400U83 lbs, maximum without battery module. Removable internal battery module is 48 lbs (131 lbs max combined weight).
Dimensions7"H x 19"W x 21"L
7"H x 19"W x 25.1"L (GUPS 2400A-104)
Internal Battery Module
Battery Description (GUPS 2400A and GUPS 2400U)192 VDC, 2.5 AH sealed lead acid
Configuration96 cells at 2.0 V, 2.5 AH in a single pullout, removable module
Recharge Time4 hours, 90% full charge with integral battery charger
Typical Minimum Hold-Up Time 2400 VA at 25°C5 minutes
Microprocessor Controlled EqualizationBatteries maintained on a temperature compensated, constant voltage float charge with automatic equalization as required
TemperatureOperating 0° to 40°C; non-operating -40° to 65°C
Weight of Removable Module48 lbs
Alarms and Signals
AlarmsThe audible alarm sounds for an overtemperature, loss of AC input or improper battery voltage.
Signals(1) Isolated relay contacts signal loss of AC input and impending inverter shutdown due to low battery capacity and
(2) RS 232 data communications for computer interface provides information on GUPS status, alarms and parameter values.
Indicators
AC InputA three color LED indicates the condition of the AC input voltage. The LED is green when the AC input voltage is within the normal operating limits, amber when the voltage is close to the limits of the operating range and red when the operating voltage range is exceeded.
BatteryA three color LED indicates the condition of the battery. The LED is green under normal operating conditions, amber when the battery is discharging or has low capacity and red when impending inverter shutdown is approached.
LoadA three color LED indicates the amount of output load.
The LED is green when the load is less than 80% of maximum output, amber when the load is within 80% to 105% and red when the load exceeds 105%, indicating that the inverter will shut down if the load is maintained.
TemperatureA two color LED indicates the overtemperature condition of the GUPS.
The LED is green under normal operating conditions and red when an over- temperature occurs.
TestA two color LED indicates the results of the internal self-test. A blinking light indicates the test is in progress.
When the test is complete, the LED turns green if the GUPS passes the test and red if it fails.
Controls
Output OnSwitches on or off the GUPS output
TestInitiates the internal self-test
Alarm SilenceSilences the audible alarm
Remote Shutdown
(GUPS 2400U only)
Switches off the UPS output and disconnects the UPS from the AC input source.
Requires external SPST contact closure
Frequency Switch
Output Frequency
(GUPS 2400U only)
Selects 50 or 60 Hz output
Configuration Terminal Block
Output Voltage
(GUPS 2400U only)
Selects 115 VAC or 230 output