| Model | AFC-31010 | AFC-31015 | AFC-31020 | AFC-31030 | AFC-31045 | AFC-31060 | AFC-31075 |
| Capacity (kVA) | 10 | 15 | 20 | 30 | 45 | 60 | 75 |
| Circuit Type | IGBT/PWM type |
| Input | Phase | Three phase |
| Wave | SINE WAVE |
| Voltage | 220V/380V |
| Voltage range | 220V/380V±15% |
| Frequency range | 50Hz±3Hz or 60Hz±3Hz |
| Power factor | 0.85 |
| Output | Phase | Single phase |
| Wave | SINE WAVE |
| Voltage | Low | 5V-150V(L-N) |
| High | 10V-300V(L-N) |
| Frequency | 47~63Hz Adjustable,50Hz,60Hz; 2F,4F,400Hz(Option) |
| Frequency regulation | ≦0.01% |
Max. current | High (A) | 41.7 | 62.5 | 83.3 | 125.0 | 187.5 | 250.0 | 312.5 |
| Low (A) | 83.3 | 125.0 | 166.7 | 250.0 | 375.0 | 500.0 | 625.0 |
| System | Line regulation | <1% |
| Load regulation | ±1% (linear load) |
| Total harmonic distortion (THD) | 2% (linear load) |
| Efficiency | ≧90% |
| Response time | ≦2ms |
| Wave factor | 3:1 |
Protection device | Input no-fuse breaker, electronic circuit instant trip for over/low voltage, over current, over load, over temperature and short circuit protection and alarm system |
| Indicator | Display | LED |
| Voltage | Show range: 0~600V, analytic degree: 0.1V, accurate degree: 0.15%FS+4COUNT |
| Current | Show range: 0~700A, analytic degree: 0.01A(<100A)/0.1A(≥100A), accurate degree: 0.2%FS+4COUNT |
| Power | Show range: 3kW~75kW, analytic degree: 0.01kW(<10kW)/0.1kW(≥10kW), accurate degree: 0.3%FS+4COUNT |
| Frequency | Show range: 0~999.9Hz, analytic degree: 0.1Hz, accurate degree: 0.1% |
| Environment | Insulation resistance | DC500V ≧ 20MΩ |
| Withstand voltage insulation | AC 1800V 5mA/ 1Min |
| Cooling system | Fan cooling |
| Temperature | 0℃~40℃ |
| Humidity | 0~90% (Non-condensing) |
| Altitude | ≦ 1500m |
| Case No. | ③ | ④ | ⑤ |
| Weight(kg) | 210 | 240 | 290 | 340 | 540 | 610 | 670 |